SERIES 5 MICRO INVERTER NEMA-1 / IP-40 Installation and Operation Manual For Catalog Number - ID5601- EO
10 SAFETY NOTICE (Continued) CAUTION! 1. Some motors have low speed characteristics, which cause overheating and winding failure under light load
11 FIGURE 1 - QUICK-START CONNECTION DIAGRAM *For 115 VAC line, install jumper J1 (supplied).Recommended Tightening Torque lb-in (7), kg
12 2.5 MOTOR CONNECTION: Connect the motor to Terminal Block TB1 (Terminals “U”, “V”, “W”), as shown in Figure 1, on page 10. (Load reactors may
13 FIGURE 3 – DRIVE LAYOUT
14FIGURE 4 – MECHANICAL SPECIFICATIONS (INCHES/MM) Side View is shown dimensioned with the cover installed.Recommended tightening torque for thetwo (
15 3 MOUNTING INSTRUCTIONS The drive is designed with a NEMA-1 / IP-40 enclosure for indoor use. It is recommended that the drive be mounted ve
16 FIGURE 6 - RUN/FAULT RELAY OUTPUT CONNECTIONS Relay CommonNormally ClosedNormally OpenTB2Recommended Tightening Torque lb-in (3.5), kg-c
17 TABLE 10 - DRIVE OPERATING CONDITION AND RUN/FAULT RELAY CONTACT STATUS Run Relay Operation (J5 Installed in “RUN” Position) (Factory Setting)
18FIGURE 7 – MAXIMUM ALLOWED MOTOR TORQUE VS. SPEED MOTOR SPEED (%)INVERTER DUTYAND TENV MOTORS0 10 20 30 40 50 60 70 80 90 100MA
19 FIGURE 10 - MOTOR HORSEPOWER SELECTION 6 SETTING SELECTABLE JUMPERS WARNING! ELECTRICAL SHOCK CAN CAUSE SERIOUS OR FATAL INJURY. BE SURE
2 TABLE OF CONTENTS Section Page 1 Introduction ...
20 6.3.1 Manual Start and Reset*: In Manual Start Mode, the drive must be manually restarted, after a fault has cleared, using the optional Forward-
21 FIGURE 16 - MINIMUM SPEED TRIMPOT RANGE (Shown Factory Set to 0% Frequency Setting) For 120 Hz output with 60 Hz motor, set Jumper J4 to t
22FIGURE 18 - ACCELERATION TRIMPOT RANGE (Shown Factory Set to 1.5 Seconds) FIGURE 19 - DECELERATION TRIMPOT RANGE (Shown Factory Set to 1.5 Sec
23 FIGURE 21 – CURRENT LIMIT TRIMPOT RANGE FIGURE 22 – I2T TRIP TIME vs. MOTOR CURRENT The slip compensation may be adjusted as follow
24 The current limit may be adjusted as follows: A. Connect an AC RMS ammeter in series with one motor phase. B. Set the
25 8.2.2 Drive Set for Manual Start and Reset *:. In Manual Start Mode, the drive must be manually restarted after a fault has cleared, using t
2610 TROUBLESHOOTING WARNING! HIGH VOLTAGE IS PRESENT IN THIS DRIVE. DISCONNECT MAIN POWER BEFORE MAKING CONNECTIONS TO THE DRIVE. THE COVER M
27 TABLE 12 - TROUBLESHOOTING GUIDE Symptom Possible Cause Suggested Solution The line fuse or circuit breaker installed is the incorrect rating.
28 TABLE 13 - FAULT RECOVERY AND RESETTING THE DRIVE* Fault Automatic Start Mode (Factory Setting) Undervoltage Drive will automatically start
29 - Notes -
3 1 INTRODUCTION Thank you for purchasing the Adjustable Frequency Drive, ID5601-EO. Baldor, Inc. is committed to providing total customer sati
30- Notes -
31 BALDOR DISTRICT OFFICES UNITED STATES ARIZONA PHOENIX 4211 S 43RD PLACE PHOENIX, AZ 85040 PHONE: 602-470-0407 FAX: 602-470-0464 ARKAN
32 LIMITED WARRANTY For a period of 2 years from the date of original purchase, Baldor will repair or replace without charge, controls which our e
4 TABLE 1 - STANDARD FEATURES Feature Description Simple to Operate Does not require programming. Uses trimpots and jumpers which are factory set f
5 TABLE 3 - PROTECTION FEATURES Feature Description Motor Overload (I2t) with RMS Current Limit Provides motor overload protection which prevents
6 TABLE 6 - OPTIONAL ACCESSORY Description Catalog No. Forward-Stop-Reverse Switch: Provides motor reversing, stop, and manual start functions. ID
7 TABLE 8- GENERAL PERFORMANCE SPECIFICATIONS Description Specification Factory Setting 115 Volt AC Line Input Voltage Operating Range (Volts A
8 SAFETY NOTICE WARNING - STATEMENT INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, COULD RESULT IN INJURY OR DEATH. CAUTI
9 SAFETY NOTICE(Continued) WARNING! HIGH VOLTAGE IS PRESENT IN THIS DRIVE. DISCONNECT MAIN POWER BEFORE MAKING CONNECTIONS TO THE DRIVE. T